List of outdoor unit anomalies
If the outdoor unit is faulty, the error code is signalled on the control panel (Fig. 21) and on the interface board (see paragraph "Interface
board - 7-segment display"). The failure is signalled in different ways.
On the control panel, the error is displayed with an “A” + error code.
On the interface board, the error is displayed with an “E” + error code, showing a sequence of two digits.
For example:
Error 101 is displayed as follows: E1 alternated with 01.
The following is the list of alarms as displayed on the control panel.
Error Code
Anomaly signalled
Indoor unit status / Solution
A101
Outdoor unit communication error
Check the communication cable to the outdoor unit. Check that
the interface board works properly.
(1)
A109
Communication error due to incorrect address of
interface board
Check the address on the interface board.
(1)
A122
MODBUS communication error
Check communication between the management board and inter-
face boards.
(1)
A162
EEPROM error
Replace the main board of the outdoor unit
(1)
A177
Emergency error
(1)
A198
Error of thermal fuse terminal board (open)
(1)
A201
Communication error (failed coupling) between
interface board and outdoor unit
Check the communication cable to the outdoor unit.
Check that the interface board and main board of the outdoor unit
work properly
(1)
A202
Communication error (failed coupling) between
indoor unit and interface board
Check the communication cable to the outdoor unit.
Check that the interface board and main board of the outdoor unit
work properly
(1)
A203
Communication error between Inverter and main
board of the outdoor unit
Check wiring of communication between the two boards.
Replace the main board.
Replace the inverter board
(1)
A221
Outdoor unit air temperature sensor error
Check the position of the sensor.
Check the relative wiring
Replace the sensor
(1)
A231
Condenser temperature sensor error
Check the position of the sensor.
Check the relative wiring
Replace the sensor
(1)
A251
Discharge temperature sensor error
Check the position of the sensor.
Check the relative wiring
Replace the sensor
(1) If the shutdown or fault persists, contact an authorised company (e.g. Authorised After-Sales Technical Assistance Centre).