Ardesto ACM-09CRN7 - Инструкция по эксплуатации - Страница 34

Кондиционеры Ardesto ACM-09CRN7 - инструкция пользователя по применению, эксплуатации и установке на русском языке. Мы надеемся, она поможет вам решить возникшие у вас вопросы при эксплуатации техники.

Если остались вопросы, задайте их в комментариях после инструкции.

"Загружаем инструкцию", означает, что нужно подождать пока файл загрузится и можно будет его читать онлайн. Некоторые инструкции очень большие и время их появления зависит от вашей скорости интернета.
Страница:
/ 64
Загружаем инструкцию
background image

34

exposed while charging, recovering or purging the system; 

That there is continuity of earth bonding.

7.Repairs to sealed components

1)During repairs to sealed components, all electrical 

supplies shall be disconnected from the equipment being 

worked upon prior to any removal of sealed covers, etc. If it

isabsolutely necessary to have an electrical supply to 

equipment during servicing, then a permanently operating 

form of leak detection shall be located at the most critical 

point to warn of a potentially hazardous situation. 

2)Particular attention shall be paid to the following to ensure

that by working on electrical components, the casing is not 

altered in such a way that the level of protection is affected. 

This shall include damage to cables, excessive number of 

connections, terminals not made to original specification, 

damage to seals, incorrect fitting of glands, etc.  

Ensure that apparatus is mounted securely. 

Ensure that seals or sealing materials have not degraded 

such that they no longer serve the purpose of preventing the

ingress of flammable atmospheres. Replacement parts shall 

be in accordance with the manufacturer's specifications.

NOTE: The use of silicon sealant may inhibit the 

effectiveness of some types of leak detection

equipment. Intrinsically safe components do not have to 

be isolated prior to working on them.

8.Repair to intrinsically safe components 

Do not apply any permanent inductive or capacitance 

loads to the circuit without ensuring that this will not 

exceed the permissible voltage and current permitted for 

the equipment in use. Intrinsically safe components are 

the only types that can be worked on while live in the 

presence of a flammable atmosphere. The test apparatus 

shall be at the correct rating. Replace components only 

with parts specified by the manufacturer. Other parts may 

result in the ignition of refrigerant in the atmosphere from 

a leak.

9.Cabling

Check that cabling will not be subject to wear, corrosion, 

excessive pressure, vibration, sharp edges or any other 

adverse environmental effects. The check shall also take

into account the effects of aging or continual vibration 

from sources such as compressors or fans.

10.Detection of flammable refrigerants

Under no circumstances shall potential sources of ignition 

be used in the searching for or detection of refrigerant 

leaks. A halide torch (or any other detector using a naked 

flame) shall not be used.

11.Leak detection methods

he following leak detection methods are deemed 

acceptable for systems containing flammable refrigerants. 

Electronic leak detectors shall be used to detect flammable

refrigerants, but the sensitivity may not be adequate, or 

Warnings(for using R290/R32 refrigerant only)

may need re-calibration. (Detection equipment shall be 

calibrated in a refrigerant-free area.) Ensure that the 

detector is not a potential source of ignition and is suitable 

for the refrigerant used. Leak detection equipment shall be 

set at a percentage of the LFL of the refrigerant and shall be 

calibrated to the refrigerant employed and the appropriate 

percentage of gas (25 % maximum) is confirmed. Leak 

detection fluids are suitable for use with most refrigerants 

but the use of detergents containing chlorine shall be 

avoided as the chlorine may react with the refrigerant and 

corrode the copper pipe-work. If a leak is suspected, all 

naked flames shall be removed/ extinguished. If a leakage 

of refrigerant is found which requires brazing, all of the 

refrigerant shall be recovered from the system, or isolated 

(by means of shut off valves) in a part of the system remote 

from the leak. Oxygen free nitrogen (OFN) shall then be 

purged through the system both before and during the 

brazing process.

12.Removal and evacuation

When breaking into the refrigerant circuit to make repairs  

or for any other purpose conventional procedures shall be 

used. However, it is important that best practice is followed

since flammability is a consideration. The following 

procedure shall be adhered to:

 Remove refrigerant; 

 Purge the circuit with inert gas;   

 Evacuate; 

 Purge again with inert gas; 

 Open the circuit by cutting or brazing. 

The refrigerant charge shall be recovered into the correct 

recovery cylinders. The system shall be flushed with OFN 

to render the unit safe. This process may need to be 

repeated several times. Compressed air or oxygen shall 

not be used for this task.  

Flushing shall be achieved by breaking the vacuum in the 

system with OFN and continuing to fill until the working 

pressure is achieved, then venting to atmosphere, and 

finally pulling down to a vacuum. This process shall be 

repeated until no refrigerant is within the system. When 

the final OFN charge is used, the system shall be vented 

down to atmospheric pressure to enable work to take 

place. This operation is absolutely vital if brazing 

operations on the pipe-work are to take place. 

Ensure that the outlet for the vacuum pump is not close to 

any ignition sources and there is ventilation available.

13.Charging procedures

In addition to conventional charging procedures, the 

following requirements shall be followed.

Ensure that contamination of different refrigerants does 

not occur when using charging equipment. Hoses or lines 

shall be as short as possible to minimise the amount of 

refrigerant contained in them. 

Cylinders shall be kept upright.

Ensure that the refrigeration system is earthed prior to 

charging the system with refrigerant.

Label the system when charging is complete (if not already).
 

6

EN

Характеристики

Оцените статью
tehnopanorama.ru
Остались вопросы?

Не нашли свой ответ в руководстве или возникли другие проблемы? Задайте свой вопрос в форме ниже с подробным описанием вашей ситуации, чтобы другие люди и специалисты смогли дать на него ответ. Если вы знаете как решить проблему другого человека, пожалуйста, подскажите ему :)

Задать вопрос

Часто задаваемые вопросы
Как посмотреть инструкцию к Ardesto ACM-09CRN7?
Необходимо подождать полной загрузки инструкции в сером окне на данной странице
Руководство на русском языке?
Все наши руководства представлены на русском языке или схематично, поэтому вы без труда сможете разобраться с вашей моделью
Как скопировать текст из PDF?
Чтобы скопировать текст со страницы инструкции воспользуйтесь вкладкой "HTML"