614-40094-00
28
1.
2.
6.7 Eaton Intelligent Power Software suite
Eaton Intelligent Power Software suite is available from
.
Eaton Software suite provides up-to-date graphics of UPS power and system data and power flow.
It also gives you a complete record of critical power events, and it notifies you of important UPS or power information.
If there is a power outage and the 5PX UPS battery power becomes low, Eaton Software suite can automatically shut
down your computer system to protect your data before the UPS shutdown occurs.
6.8 Cybersecurity
Eaton is committed to minimizing the Cybersecurity risk in its products and employs cybersecurity best practices and the
latest cybersecurity technologies in its products and solutions, making them more secure, reliable and competitive for
our customers. Eaton also offers Cybersecurity Best Practices whitepapers to its customers, referenced at
.
7 Operation
7.1 Start-up and normal operation
Check that the indications on the name plate located on the back of the UPS meets to the AC power source and the
true electrical consumption of the total load.
Battery charge
The UPS charges the battery as soon as it is connected to the AC outlet, whether the ON/OFF button is pressed or not. It is
recommended that the UPS be permanently connected to the AC power supply to ensure the best possible autonomy.
On the first startup of the UPS, you will need to configure the output voltage and time of the UPS.
To start the UPS:
1. Verify that the UPS power cord is plugged in.
2. The UPS front panel display illuminates and shows Eaton logo.
3. Verify that the UPS status screen shows
.
4. Press the
button on the UPS front panel for at least two seconds.
5. Check the UPS front panel display for active alarms or notices. Resolve any active alarms before continuing; if the
indicator is on, do not proceed until all alarms are clear (see "
" section). Check the UPS status from the
front panel to view the active alarms. Correct the alarms and restart if necessary.
6. Verify that the
indicator illuminates solid, indicating that the UPS is operating normally and any loads are powered
and protected. The UPS should be in Normal mode.
7.2 Starting the UPS on battery
Before using this feature, the UPS must have been powered by utility power with output enabled at least once.
Battery start can be disabled. See the "Cold start" setting in "
".
To start the UPS on battery:
When the UPS is disconnected from the AC power source, press the
button on the UPS front panel.
The UPS transfers from Standby mode to Battery mode. The
indicator illuminates solid.
The UPS supplies power to your equipment.
Check the UPS front panel display for active alarms or notices besides the "Battery mode" and related notifications
that indicates missing utility power. Resolve any active alarms before continuing. See "
Check the UPS status from the front panel to view the active alarms. Correct the alarms and restart if necessary.