Easy UPS SRV Series Rack-Mount 6000VA, 10000VA
Connect power and equipment to the UPS
CAUTION
HAZARD OF ELECTRIC SHOCK
•
All electrical work must be performed by a qualified electrician.
•
Adhere to all national and local electrical codes.
•
Disconnect the mains power and internal batteries before installing or servicing the UPS or connected equipment.
•
UPS AC hardwired and pluggable outlets may be energized by remote or automatic control at any time.
•
Do not use the UPS as safety disconnect.
•
Turn off all power to this equipm ent before working on the equipm ent. Practice lockout/tagout procedures.
•
Do not wear jewelry when working with electrical equipment.
Failure to follow these instructions can result in minor or moderate injury.
1.
Connect equipment to the UPS. Avoid using extension cords.
2.
Connect input utility power to the UPS.
3.
Switch on the input utility power. Then, the UPS display panel will illuminate when utility power is available.
Start the UPS
Press the
button located on the front panel of the UPS.
The battery charges to 90% capacity during the first five hours of normal operation.
Do not
expect full battery run capability during this initial charge period.
Cold start the UPS
Use cold start feature to supply power to connected equipment from the UPS batteries.
Press the
button. Then, the display panel will illuminate. Press the
button again
to supply
battery power to the connected equipment.
Connect and install management software
Easy UPS SRV is provided with SchneiderUPS management software for unattended operating system shutdown,
UPS monitoring, UPS control and energy reporting. The following diagram is a representation of a typical server
installation.
1.
Connect the USB cable from the rear of the
UPS
to the protected device such as a
server.
2.
For a server or other device with an
operating system, load the SchneiderUPS
CD and follow the on-screen set-up
instructions.
3.
A built-in serial port
is also
available for additional communication
options with serial cable.
4.
Even more communication options are
available via the built-in intelligent card
slot. Refer to www.apc.com for more
information.