6.  No ignition sources 

No  person  carrying  out  work  in  relation  to  a  refrigeration  system  which  involves 
exposing any pipe  work that contains or  has contained flammable refrigerant shall  use 
any sources of ignition in such a manner that it may lead to the risk of fire or explosion. 
All possible ignition sources, including cigarette smoking, should be kept sufficiently far 
away  from  the  site  of  installation,  repairing,  removing  and  disposal,  during  which 
flammable refrigerant can possibly be released to the surrounding space. Prior to work 
taking place, the area around the  equipment is to be surveyed to make sure that there 
are no flammable hazards or ignition risks. 

“No Smoking” signs shall be displayed. 

 

7.  Ventilated area 

Ensure  that  the  area  is  in  the  open  or  that  it  is  adequately  ventilated  before  breaking 
into  the  system  or  conducting  any  hot  work.  A  degree  of  ventilation  shall  continue 
during  the  period  that  the  work  is  carried  out.  The  ventilation  should  safely  disperse 
any released refrigerant and preferably expel it externally into the atmosphere.  
 

8.  Checks to the refrigeration equipment 

Where  electrical  components  are  being  changed,  they  shall  be  fit  for  the  purpose  and 

to  the  correct  specification.  At  all  times  the  manufacturer’s  maintenance  and  service 
guidelines  shall  be  followed.  If  in  doubt  consult  the  manufacturer

’s  technical 

department for assistance. 
The following checks shall be applied to installations using flammable refrigerants:  

–  The  charge  size  is  in  accordance  with  the  room  size  within  which  the  refrigerant 
containing parts are installed; 

–  The  ventilation  machinery  and  outlets  are  operating  adequately  and  are  not 
obstructed; 

– If an indirect refrigerating circuit is being used, the secondary circuit shall be checked 
for the presence of refrigerant; 

– Marking to the equipment continues to be visible and legible. Markings and signs that 
are illegible shall be corrected; 

– refrigeration pipe or components are installed in a position where they are unlikely to 
be  exposed  to  any  substance  which  may  corrode  refrigerant  containing  components, 
unless  the  components  are  constructed  of  materials  which  are  inherently  resistant  to 
being corroded or are suitably protected against being so corroded.  
 

9.  Checks to electrical devices 

Repair  and  maintenance  to  electrical  components  shall  include  initial  safety  checks 
and  component  inspection  procedures.  If  a  fault  exists  that  could  compromise  safety, 
then  no  electrical  supply  shall  be  connected  to  the  circuit  until  it  is  satisfactorily  dealt 
with.  If  the  fault  cannot  be  corrected  immediately  but  it  is  necessary  to  continue  
operation, an adequate temporary solution shall be used. This shall  be reported to the 
owner of the equipment so all parties are advised. 
Initial safety checks shall include: 
-those  capacitors  are  discharged:  this  shall  be  done  in  a  safe  manner  to  avoid 
possibility of sparking; 
-that  there  no  live  electrical  components  and  wiring  are  exposed  while  charging, 
recovering or purging the system; 
-that there is continuity of earth bonding 
 

10. Maintenance of sealed components 

It  is  important  to  ensure  that  all  power  sources  are  disconnected  from  the  operating 
equipment during the maintenance of sealed components, before removing the sealing 
covers, etc. 

Содержание

Полезные видео

Характеристики

Оцените статью
tehnopanorama.ru
Остались вопросы?

Не нашли свой ответ в руководстве или возникли другие проблемы? Задайте свой вопрос в форме ниже с подробным описанием вашей ситуации, чтобы другие люди и специалисты смогли дать на него ответ. Если вы знаете как решить проблему другого человека, пожалуйста, подскажите ему :)

Задать вопрос

Часто задаваемые вопросы
Как посмотреть инструкцию к Timberk T-PAC12-P11E?
Необходимо подождать полной загрузки инструкции в сером окне на данной странице
Руководство на русском языке?
Все наши руководства представлены на русском языке или схематично, поэтому вы без труда сможете разобраться с вашей моделью
Как скопировать текст из PDF?
Чтобы скопировать текст со страницы инструкции воспользуйтесь вкладкой "HTML"