11. Appendix
NO.
Description
Record
1
Is the unit in good condition and without any visible damage?
⧠
Yes
2
Has the unit been transported in upward position?
⧠
Yes
3
Is the crankcase oil level between ¼ and ¾ of the compressor sight glass?
⧠
Yes
4
Is the power supply on site in line with the unit specification?
⧠
Yes
5
Is air short circuit and/or air blockage avoided?
⧠
Yes
6
Is the location well ventilated?
⧠
Yes
7
Is there sufficient space for air flow and maintenance?
⧠
Yes
8
Is all the pre-charged nitrogen released before the field pipe connection started?
⧠
Yes
9
Has nitrogen been blown through the pipes during brazing?
⧠
Yes
10
Is there only 1 indoor unit connected to the CDU?
⧠
Yes
11
Does the field piping has the same diameter as the pipes coming from CDU?
⧠
Yes
12
Is the suction pipe insulated?
⧠
Yes
13
Does the bends have enough bending radius?
⧠
Yes
14
Is the total pipe length less than 25m?
⧠
Yes
15
Is the height difference within the specifications [refer page 7]
⧠
Yes
16
Are the oil traps in the vertical suction line correctly positioned? [refer page 3]
⧠
Yes
17
Does the CDU capacity matches the indoor unit capacity?
⧠
Yes
18
Does the TXV capacity matches the indoor unit capacity?
⧠
Yes
19
Is the TXV sensing bulb fixing in good position/condition?
⧠
Yes
20
Is there a MOP expansion valve installed? [refer page 3]
⧠
Yes
21
Was inert, dry gas (e.g. Nitrogen) used when pressure testing?
⧠
Yes
22
Could the leak test pressures be reached?
⧠
Yes
23
Did the test pressure stayed stable after at least 24 hours?
⧠
Yes
24
Could the vacuum condition (< -0.1 barg for 2 hours) be reached?
⧠
Yes
25
Did the pressure stayed stable for at least 1 hour, when turning off the vacuum
pump?
⧠
Yes
26
Is the high/low pressure safety on the pressure switch set correctly? [refer page4]
⧠
Yes
27
Is the fan speed controller set correctly? [refer page 4]
⧠
Yes
28
Is the correct circuit breaker been used?
⧠
Yes
29
Is there an earth connection foreseen?
⧠
Yes
30
Are all terminal connections good/tight connected?
⧠
Yes
31
Is the crankcase heater been energized for minimum 12 hours before start up?
⧠
Yes
32
Is the refrigerant correct for intended use?
⧠
Yes
33
Is the high pressure above the minimum limit when charging the system? [refer page 5]
⧠
Yes
34
Is the refrigerant charge amount correct (clear sight glass)?
⧠
Yes
Remarks: the system may only be started up if all questions can be answered with “Yes”.