250/500 kW 400/480 V
NOTE:
Schneider Electric recommends that each UPS in the parallel system
has a neutral connection installed. Contact Schneider Electric for information
on other configurations.
Recommended Fuses, Breakers, and Cable Sizes in the US
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The product must be installed according to the specifications and requirements
as defined by Schneider Electric. It concerns in particular the external and
internal protections (upstream circuit breakers, battery circuit breakers, cabling,
etc.) and environmental requirements. No responsibility is assumed by
Schneider Electric if these requirements are not respected.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
All wiring must comply with all applicable national and/or local electrical codes.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Appropriate disconnect devices must be provided external to the equipment.
Failure to follow these instructions will result in death or serious injury.
NOTE:
See
Required Breaker Settings for Input Overload and Short-Circuit
Protection for Breakers with Electronic Trip Units, page 34
for information on
breaker settings.
Temperature rating of conductors is 90 °C/194 °F and with 75 °C terminations.
Refer to table 310-16 of NEC, 75 °C column for maximum ampacity. Use only
copper conductors.
Equipment grounding conductors are sized in accordance with NEC Article 250-
122 and Table 250-122.
The cable sizes are recommendations for maximum configurations with three
current carrying conductors in a raceway. For other configurations see the label
inside the front door of the I/O cabinet.
30
990-3880G-001