Air Evacuation

 

Preparations and Precautions

Air and foreign matter in the refrigerant circuit can 
cause abnormal rises in pressure, which can damage 
the air conditioner, reduce its efficiency, and cause
injury. Use a vacuum pump and manifold gauge to 
evacuate the refrigerant circuit, removing any 
non-condensable gas and moisture from the system.      

Evacuation should be performed upon initial 
installation and when unit is relocated. 

BEFORE PERFORMING EVACUATION

  

Check to make sure the connective pipes

between the indoor and outdoor units 

are connected properly . 

  

Check to make sure all wiring is connected 

properly.

Evacuation Instructions

Manifold Gauge

Compound 

gauge

-76cmHg

Low pressure 

valve

High pressure

valve

Pressure hose / 

Charge hose

Charge hose

V

acuum

pump

Pressure gauge

Low pressure valve

1.

 

Connect the charge hose of the manifold 

gauge to service port on the outdoor unit’s 

low pressure valve. 

Connect another charge hose from the 

manifold gauge to the vacuum pump. 

Open the Low Pressure side of the manifold 
gauge. Keep the High Pressure side closed. 
Turn on the vacuum pump to evacuate the 
system.
Run the vacuum for at least 15 minutes, or
until the Compound Meter reads -76cmHG
(-10  Pa).    

  

2.

 

3.

 

4.

 

5.

5

6.

 

Close the Low Pressure side of the manifold 

gauge, and turn off the vacuum pump.

7.

 

Wait for 5 minutes, then check that there 

has been no change in system pressure.

8.

 

If there is a change in system pressure, refer 

to Gas Leak Check section for information 

on how to check for leaks. If there is no 

change in system pressure, unscrew the cap 

from the packed valve (high pressure valve).

9.

 

Insert hexagonal wrench into the packed valve 

(high pressure valve) and open the valve by 

turning the wrench in a 1/4 counterclockwise 

turn. Listen for gas to exit the system, then 

close the valve after 5 seconds.

10. 

Watch the Pressure Gauge for one minute 

to make sure that there is no change in 

pressure. The Pressure Gauge should read 

slightly higher than atmospheric pressure.

Flare nut

Cap

valve body

valve stem

11.

 

Remove the charge hose from the service port.

12.  

Using hexagonal wrench, fully open both the 

high pressure and low pressure valves.

13.  

Tighten valve caps on all three valves (service 

port, high pressure, low pressure) by hand. 

You may tighten it further using a torque 

wrench if needed.

 OPEN VALVE STEMS GENTLY

 

When opening valve stems, turn the hexagonal 

wrench until it hits against the stopper. Do not 

try to force the valve to open further.

Air Evacuation

Характеристики

Оцените статью
tehnopanorama.ru
Остались вопросы?

Не нашли свой ответ в руководстве или возникли другие проблемы? Задайте свой вопрос в форме ниже с подробным описанием вашей ситуации, чтобы другие люди и специалисты смогли дать на него ответ. Если вы знаете как решить проблему другого человека, пожалуйста, подскажите ему :)

Задать вопрос

Часто задаваемые вопросы
Как посмотреть инструкцию к Neoclima NS-09?
Необходимо подождать полной загрузки инструкции в сером окне на данной странице
Руководство на русском языке?
Все наши руководства представлены на русском языке или схематично, поэтому вы без труда сможете разобраться с вашей моделью
Как скопировать текст из PDF?
Чтобы скопировать текст со страницы инструкции воспользуйтесь вкладкой "HTML"