Smart-UPS On-Line SRT1000/SRT1500 XLI Tower/Rack-Mount 2U

2

Safety and General Information

•  Adhere to all national and local electrical codes.
•  All wiring must be performed by a qualified electrician.
•  Changes and modifications to this unit not expressly approved by APC could void the warranty.
•  This UPS is intended for indoor use only. 
•  Do not operate this UPS in direct sunlight, in contact with fluids, or where there is excessive dust or 

humidity.

•  Be sure the air vents on the UPS are not blocked. Allow adequate space for proper ventilation.
•  For a UPS with a factory installed power cord, connect the UPS power cable directly to a wall outlet. Do not 

use surge protectors or extension cords.

•  The equipment is heavy. Always practice safe lifting techniques adequate for the weight of the equipment.
•  The batteries are heavy. Remove the batteries before installing the UPS and external battery packs (XLBPs), 

in a rack.

•  Always install XLBPs at the bottom in rack-mount configurations. The UPS must be installed above the 

XLBPs.

•  Always install peripheral equipment above the UPS in rack-mount configurations.
•  Additional safety information can be found in the Safety Guide supplied with this unit.

Deenergizing safety

•  

T

he UPS contains internal batteries and may present a shock hazard even when disconnected from AC and 

DC power.

•  The AC and DC output connectors may be energized by remote or automatic control at any time. 
•  Before installing or servicing the equipment check that the:

– Input circuit breaker is in the 

OFF

 position.

– Internal UPS batteries are removed.
– XLBP battery modules are disconnected.

Electrical safety

•  For models with a hardwired input, the connection to the branch circuit (mains) must be performed by a 

qualified electrician.

•  Have a proper grounding for input socket for the models with pluggable power cords.
•  The protective earth conductor for the UPS carries the leakage current from the load devices (computer 

equipment). An insulated ground conductor is to be installed as part of the branch circuit that supplies the 
UPS. The conductor must have the same size and insulation material as the grounded and ungrounded 
branch circuit supply conductors. The conductor will typically be green and with or without a yellow stripe.

•  The UPS input ground conductor must be properly bonded to protective earth at the service panel.
•  If the UPS input power is supplied by a separately derived system, the ground conductor must be properly 

bonded at the supply transformer or motor generator set.

•  Leakage current for a pluggable Type A UPS may exceed 3.5 mA when a separate ground terminal is used.

Характеристики

Оцените статью
tehnopanorama.ru
Остались вопросы?

Не нашли свой ответ в руководстве или возникли другие проблемы? Задайте свой вопрос в форме ниже с подробным описанием вашей ситуации, чтобы другие люди и специалисты смогли дать на него ответ. Если вы знаете как решить проблему другого человека, пожалуйста, подскажите ему :)

Задать вопрос

Часто задаваемые вопросы
Как посмотреть инструкцию к APC 1500?
Необходимо подождать полной загрузки инструкции в сером окне на данной странице
Руководство на русском языке?
Все наши руководства представлены на русском языке или схематично, поэтому вы без труда сможете разобраться с вашей моделью
Как скопировать текст из PDF?
Чтобы скопировать текст со страницы инструкции воспользуйтесь вкладкой "HTML"