Back-UPS Pro BR650MI / BR900MI / BR1300MI / BR1600MI
9
Troubleshooting
Problem
Possible Cause
Corrective Action
Back-UPS will not
switch on.
The Back-UPS is not connected to
AC power.
Ensure that the Back-UPS is securely
connected to an AC outlet.
The circuit breaker has been
tripped.
Disconnect non-essential equipment
from the Back-UPS. Reset the circuit
breaker. Re-connect equipment one
item at a time. If the circuit breaker is
tripped again, disconnect the device
that caused the trip.
The internal battery is not
connected.
Connect the battery.
The AC input voltage is out of
range.
Adjust the transfer voltage and
sensitivity range.
The Back-UPS
does not provide
power during a AC
power outage.
Ensure that essential equipment is
not
plugged into a
Surge Only
outlet.
Disconnect equipment from the
Surge Only
outlet and re-connect to a
Battery Backup outlet.
The Back-UPS is
operating on
battery power,
while connected to
AC power.
The plug has partially pulled out of
the wall outlet, the wall outlet is no
longer receiving AC power, or the
circuit breaker has been tripped.
Ensure that the plug is fully inserted
into the wall outlet. Ensure that the
wall outlet is receiving AC power by
checking it with another device.
The Back-UPS is performing an
automatic self test.
No action is necessary.
The AC input voltage is out of
range, the frequency is out of
range, or the waveform is distorted.
Adjust the transfer voltage and
sensitivity range.
The Back-UPS
does not provide
the expected
amount of backup
time.
Battery Backup outlets may be
fully or improperly loaded.
Disconnect non-essential equipment
from the Battery Backup outlets and
connect the equipment to
Surge
outlets.
The battery was recently
discharged due to a power outage
and has not fully recharged.
Charge the battery cartridge for 16
hours.
The battery has reached the end of
its useful life.
Replace the battery.
The
Replace
Battery
indicator is
illuminated.
The battery has reached the end of
its useful life.
Replace the battery as early as
possible.
The
Overload
indicator is
illuminated.
The equipment connected to the
Back-UPS is drawing more power
than the Back-UPS can provide.
Disconnect non-essential equipment
from the Battery Backup outlets and
connect the equipment to
Surge
outlets.
The
System Error
icon is illuminated,
other icons in the
front panel are
flashing.
There is an internal detected error. Determine which internal error
message is displayed by matching
the number displayed on the LCD
with the corresponding Error
Message (see
) and contact SEIT Technical
Support.