Safety caution

This UPS utilizes voltage that may be hazardous. Do not attem pt

to disassem ble the unit. The unit contains no user replaceable

parts. Only factory service personnel m ay perform repairs.

This pluggable type A equipm ent with battery already installed by

the supplier is operator installable and m ay be operated by

laym en.

The m ains socket outlet that supplies the UPS shall be installed

near the UPS and shall be easily accessible.

During the installation of this equipm ent it should be assured that

the sum of the leakage currents of the UPS and the connected

loads does not exceed 3.5m A.

Connection to any other type of receptacle other than a t wo-pole,

three-wire grounded receptacle m ay result in shock hazard as

well as violate local electrical codes.

In the event of an em ergency, press the "OFF" button and

disconnect the power cord from the AC power supply to properly

disable the UPS.

Do not allow any liquids or any f oreign object to enter the UPS.

Do not place beverages or any other liquid -containing vessels on

or near the unit.

This unit intended for installation in a controlled environm ent

(tem perature controlled, indoor area free of cond uctive

contam inants). Avoid installing the UPS in locations where there

is standing or running water, or excessive hum idity.

Do not plug the UPS input into it s own out put.

Do not attach a power strip or surge suppressor to the UPS.

Do not attach non -com puter-related item s, such as m edical

equipm ent, life-support equipm ent, m icrowave ovens, or vacuum

cleaners to UPS.

Do not dispose of batteries in a fire as they m ay explode.

Internal battery voltage is 12VDC.Sealed, lead -acid, 6-cell battery.

A battery can present a risk of electrical shock and high short

circuit current. The following precautions should be observed

when working on batteries:

1) Rem ove watches, rings, or ot her m etal objects from the hands.

2) Use tools with insulated handles.

3) W ear rubber gloves and boot s.

4) Do not lay tools or m etal parts on top of batteries.

5) Disconnect charging source prior to connecting or

disconnecting batteries term inal.

Servicing of batteries should be perform ed or supervised by

personnel knowledgeable of bat teries and the required

precautions. Keep unauthorized personnel away from batteries.

W hen replacing batteries, replace with the sam e num ber and type

of sealed lead-acid battery.

Do not open or m utilate the battery or batteries. Release

electrolyte is harm ful to the skin and eyes. It m ay be toxic.

Attention, hazardous through electric shock. Also with dis -

connection of this unit from the m ains, hazardous voltage still may

be accessible through supply from battery. The battery supply

should be therefore disconnec ted in the plus and m inus pole at

the connectors of the battery when m aintenance or service work

inside the UPS is necessary.

To reduce the risk of overheating the UPS, do not cover the UPS'

cooling vents and avoid exposing the unit to direct sunlight or

installing the unit near heat em itting appliances such as space

heater or furnaces.

Unplug the UPS prior to cleaning and do not use liquid or spray

detergent.


Troubleshooting

Problem

Possible Cause

Solutions

Nothing is
displayed on
LCD panel.

The UPS is not
on.

Press the power switch again to
turn on the UPS.

Battery voltage
is too low.

Charge the battery at least 6
hours.

Battery fault.

Replace the battery.

The UPS
always on
battery m ode.

Power cord
loose.

Re-plug the power cord.

The UPS
continuously
beeps.

Please check
the fault code
for the details.

Please check the fault code for
the details.

Backup tim e
too short.

Battery voltage
is too low.

Charge the battery at least 6
hours.

Overload.

Rem ove som e unnecessary
loads. Before reconnecting
equipm ent, please verif y that the
load m atches the UPS capability
specified in the specs.

Battery defect.

Replace the battery.

Specification

400VA/600VA/800VA

Model

iFP 400

iFP 600

iFP 800

Capacity

400VA/

240W

600VA/

360W

800VA/

480W

Input voltage

220/230/240 Vac

Input Voltage
Range

140-290 Vac

Output Voltage
Regulation

±

10%(bat m ode)

Transfer Tim e

Typical 2-6 m s

Waveform

Sim ulated Sinewave

Battery Type

12V/4.5Ah

12V/7Ah

12V/9Ah

Battery Num ber

1

1

1

Charging Tim e

4 hours recover to 90% capacity

Dim ension(mm )

300 x 101 x 142

Net Weight (kgs)

3.55

4.2

4.9

Hum idity

0-90% RH @ 0-40°C non-condensing)

Noise Level

Less than 40dB

*Specifications are subject to change without notice.

1000VA/1500VA/2000VA

Model

iFP 1000

iFP 1500

iFP 2000

Capacity

1000VA/

600W

1500VA/

900W

2000VA/

1200W

Input voltage

220/230/240 Vac

Input Voltage
Range

140-290 Vac

Output Voltage
Regulation

±

10%(bat m ode)

Transfer Tim e

Typical 2-6 m s

Waveform

Sim ulated Sinewave

Battery Type

12V/7Ah

12V/9Ah

12V/9Ah

Battery Num ber

2

2

2

Charging Tim e

4-6 hours recover to 90% capacity

Dim ension(mm )

320 x 130 x 182

Net Weight (kgs)

8.2

10.4

11

Hum idity

0-90% RH @ 0-40°C non-condensing)

Noise Level

Less than 40dB

*Specifications are subject to change without notice.